Connect via pluggable, color-coded terminal blocks (12 to 28 AWG wire). Ensure you use only certified M25 cable glands to maintain the unit's explosion-proof rating.

Access the main terminal block by unscrewing the housing cover and removing the display module (secured by captive screws). The XNX operates on 24VDC nominal power (16 to 32VDC range). Terminal Block Configuration

The Xnx Universal Transmitter can be installed in a variety of configurations, including wall-mounted, panel-mounted, or pipe-mounted. Here are the general steps for installing the device: Xnx Universal Transmitter Quick Start Guide

Apply the span gas from the cylinder regulated to 500 mL/min.

Leave sufficient clearance beneath the unit to allow for sensor cartridge replacement and calibration adapter attachment. Mounting Steps Connect via pluggable, color-coded terminal blocks (12 to

Select from the menu immediately following the zero step.

Do not mount the cover yet. Perform these three tests: The XNX operates on 24VDC nominal power (16 to 32VDC range)

: Insert the sensor module into the dedicated bottom socket.

Follow the on-screen prompts to "Zero" the sensor in clean air.